Cables
This form is the acceptance record of power-limited and communications cabling: Class 1, Class 2 and Class 3 circuits, power-limited fire alarm, Class 4 fault-managed power, communications circuits, and the structured copper, single-pair and optical fiber links that carry them. Three things are graded: the certified field tester's verdict on every copper link at the limit it was set to, with the worst margins from the export regraded against the TIA 568.2-E equations; the Tier 1 insertion loss of every fiber against the link loss budget; and a Class 2 or Class 3 power source against its NFPA 70 (NEC) Chapter 9 Table 11 column. The installation itself - listing marking for the space, separation, support, routing, firestopping, labeling, bonding, jacket identification - is recorded against the code clauses of the edition in force and the project documents, and a shortcoming there raises a repair issue rather than setting the verdict. Power cables rated 1000 V and below belong on the low-voltage cable acceptance form, fiber transmission testing beyond the Tier 1 record on the fiber-optic cable form, and coaxial cabling on its own form.
A structured cabling link is accepted on numbers, not on appearance: a certified tester sweeping the link to its category's top frequency, and a loss test set reading a fiber against a budget built from its length, its connections and its splices. The record keeps those numbers together with what makes them meaningful - the limit the tester was set to, its accuracy level and sweep range, the reference method and launch condition behind a fiber reading, and the export that holds the full result - so a Pass certifies the installed category and link model and not a looser one. The power source matters as much as the cable: a Class 2 or Class 3 circuit is safe only because its listed source cannot exceed the Table 11 limits for its class and voltage, so the marked ratings and the measured open-circuit voltage and limited current are checked against that column. The export is the record; the rows on the form are the witness sample.
The record is made at acceptance of an installed cabling system, after termination and before handover, with the tester export and the design documents it rests on referenced from the form. Residential work under TIA 570-E is inspected before the insulation goes in, at rough-in, and tested at trim-out, where each data run needs a qualification or characterization result before the record can pass; the rough-in record is referenced where the visit was split. A fire alarm or other life-safety circuit is functionally tested under its own governing standard, and that test is referenced here, not repeated. No recurring interval is part of this form.
Identification sets the NEC edition in force, the circuit class, the media, the cabling subsystem (horizontal, backbone or centralized fiber), the listing marking as printed and the category or fiber type. The visual and mechanical checklist records each item against the clauses for the edition in force and the project documents; bend radius, untwist and termination limits come from the manufacturer data, with the TIA 568.0-E installation values where the maker gives none. For a Class 2 or Class 3 source the listing marking, output kind, marked voltage, VA and current, limiting method, measured open-circuit voltage and measured short-circuit or limited current are entered and the form finds the Table 11 column for the class, supply and voltage; Class 1, fire alarm, Class 4 and communications sources are recorded against their marking with the governing article named. Copper links are tested on a certified field tester at the TIA 568.2-E permanent link or channel limit for the installed category, with tester identity and settings recorded; per link the wiremap, the tester verdict, length, insertion loss, delay, skew, dc loop resistance and the overall worst margin are entered, and the export section carries each parameter's worst margin, frequency and limit for the regrade. Fiber links are measured for Tier 1 insertion loss by the TIA 526-14-D multimode or TIA 526-7-A single-mode method: the reference method is matched to the configuration (one, two or three cords, or the equipment cord method), the launch condition and cords are recorded, and each fiber is entered with wavelength, direction, reference power, length, inner connections, splices and measured loss against the budget from the project design or the TIA 568.3-E default. Horizontal and centralized fibers need one wavelength in one direction; backbone fibers need both wavelengths of the fiber type in at least one direction. Single-pair runs under TIA 568.5 are recorded, not graded. Functional verification closes the record: end-to-end function, the life-safety test reference and as-built drawings and labels.
Identification: NEC edition, system served, circuit class, media, subsystem, building and plant type, test stage and residential grade, listing marking, category or fiber type, construction, origin and destination. The visual checklist, jacket color and print, and the outside plant bend and untwist grades. Power source type, governing article, listing and marking, output, marked voltage, VA and current, limiting, measured open-circuit voltage and limited current, and the computed Table 11 limits and margins. Copper: link configuration, test limit, adapter, tester identity, calibration and settings; per link the ID, wiremap, verdict, length, the transmission parameters at their worst case, and the worst margin; the per-parameter regrade rows; cords, intermediate connectors, access point runs, application, export counts. Fiber: method, configuration, reference method, launch, cords, loss test set and calibration, budget basis; per fiber the ID, position and color, wavelength, direction, reference power, length, connections, splices, budget, loss and margin; polarity and counts. Single-pair rows. Functional checks, tested by, test date, the project document references, ambient conditions, test equipment, comments and deficiencies.
Every rule below must pass. Copper: every recorded link passed on the certified tester at the limit selected; no link reported a wiremap fault; insertion loss, delay, skew and dc loop resistance sit within the TIA 568.2-E field limits for the category and link model; each parameter's worst margin from the export regrades at or above zero against the 568.2-E equations at the frequency the tester reports, where return loss is not failed if insertion loss there is under 3 dB and NEXT is never excused; a marginal fail counts as a fail; and the export reconciles, links tested equal to passed plus failed, with no link reported failed. A Pass certifies only at a limit that suits the record: a lower category, the other link model, or a Category 8 limit on Category 6 or 6A fails with an issue. Fiber: every fiber's Tier 1 loss is at or below its budget to 0.01 dB, equal passing, the budget built from length, inner connections, splices and the test-cord term; fibers tested equal passed plus failed with none failed; a backbone fiber missing its second wavelength leaves the record incomplete, as does a residential data run with no final test result. Power source: a Class 2 or Class 3 source must be listed and marked, its marked VA and current within the nameplate limits of its Table 11 column, its open-circuit voltage within the column, and an inherently limited source's measured current within its limit; a source with no column raises an issue and grades nothing. Outside plant twisted pair: bend radius and untwist at splices within TIA 758-B, where an unsatisfactory fails the record. Everything else - the visual checklist, lengths and cord allowances, tester accuracy level and sweep, launch condition and cords, calibration dates, identifiers, jacket color, application distances, single-pair transmission - is raised as an issue and never sets the verdict.
UltraDb references ASTM, ANSI, IEEE, NETA, NFPA, NEMA, FAA, TIA, and IEC standards descriptively, to identify the published methods its forms are built from. UltraDb and Verlecta are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, NFPA, NEMA, FAA, TIA, IEC, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies. Where a standard is sold through the ANSI webstore, Verlecta may earn a commission on a purchase made through our link, at no extra cost to you. A commission never decides which standards we cite or how a form is built.