Insulated Bearing Insulation Resistance Testing on Motors and Generators

Insulated bearing insulation resistance testing checks the insulating layer that isolates a motor or generator bearing, or its housing, from the frame. A good layer blocks circulating shaft currents that would otherwise pit and flute the bearing, so the test protects rotating machines from a costly and often hidden failure.

Insulation resistance climbing over the test as the insulation absorbs charge; the marked readings give the polarization index.

What it is

An insulated bearing insulation resistance test checks the electrical isolation built into one end of a motor or generator. On many larger machines, and on machines fed by variable-frequency drives, one bearing or its housing is insulated from the frame, and sometimes the oil piping, seals and instrument leads at that end are insulated as well. The insulation is there to break a path for unwanted current along the shaft. The test uses a direct-voltage insulation tester connected between the insulated component, such as the bearing housing, the pedestal or the bearing shell, and the machine frame or the shaft. A high reading shows that the isolation is sound, while a low reading shows that something has bridged it or that the insulation is damaged. The test is performed on new machines at acceptance, after bearing work or reassembly, and as part of the maintenance of machines known to be prone to shaft currents. It is quick, but it must be arranged carefully, because several parts of the machine can short the insulation without the insulation itself being at fault.

Why it is done

A rotating machine can generate a voltage along its shaft because of magnetic asymmetry, because of the fields produced by a drive, or because of static charge. If the shaft is grounded at both ends through the bearings, that voltage can drive a circulating current through the bearings and the frame. The current passes through the thin oil film in the bearing, arcs across it and erodes the metal in small pits, which can progress to a pattern of grooves called fluting. The lubricant is also degraded by the arcing. The result is noise, vibration, overheating and, eventually, bearing failure that may happen suddenly and cost an unplanned shutdown. Insulating one end of the machine interrupts the circulating path. The insulation only works as long as it stays intact and is not bridged, so the test verifies that it is effective after installation and after any work that might compromise it, and it confirms that no bridge has been created by a leftover wire, a misplaced seal, a grounded sensor lead or a conductive coating of dirt.

The principle

The test is an application of insulation resistance measurement to a deliberately limited insulation path. A direct voltage is applied across the insulating layer and the instrument measures the small current that flows, reporting it as a resistance. Healthy insulation passes a negligible current and reads very high. If a bridge exists, because a bolt is not insulated, an oil pipe touches the frame or a sensor lead is grounded, the current finds a path around the insulation and the reading drops. If the insulation itself is cracked, wet, carbonized or contaminated with oil and dust, the reading also drops. The measurement can be affected by the oil film in the bearing, which acts as an insulator when the shaft is at rest and the film is in place, or which may be broken at low speed. Because the insulation on a bearing is a thin layer that was designed for a modest voltage, the test voltage must be chosen to stay safely within its rating, and a voltage that is too high can damage the very layer being tested.

How it is performed

The machine is de-energized, isolated from every source, grounded and locked out. All connections that could short the insulation are identified and opened for the test: oil lines that connect to the frame, bearing temperature detectors and vibration probes whose leads are grounded, grounding brushes or shaft-grounding devices at that end, and any bolts or pins that bypass the insulating sleeves. The insulated component is cleaned and dried, since oil and carbon dust provide a leakage path across insulating surfaces. A direct-voltage insulation tester, in calibration and set to a voltage that suits the rating of the bearing insulation, is connected between the insulated component and the frame or shaft as the construction requires. The voltage is applied for a timed interval and the reading is observed. Where the machine's design makes a difference, the shaft position and the presence of the oil film are noted, and the test is repeated after the oil film is in place or after the shaft is turned if the procedure calls for it. After the test the instrument is discharged, every lead and connection that was opened is restored, and a final check confirms that the isolation is the only thing separating the bearing from the frame.

What is recorded

The record states the machine identification, which end and which component were tested, the instrument and its calibration, the direct voltage and how long it was held, and the resistance observed. It notes which connections were opened to isolate the bearing and confirms they were restored, such as oil piping, sensors, grounding devices and bolts. The condition of the surfaces and the presence or absence of oil film are noted, as are the temperature and humidity. If readings were repeated after a change in shaft position or a cleaning, each is recorded. These details allow a later reviewer to tell a genuine loss of insulation from a bridge created by a connection that was left in place or by contamination on the surface.

How results are judged

A reading is judged on the shape of the result, and this page gives no value. The principal criterion is that the insulating layer shows a high resistance, as defined by the governing standard or the machine manufacturer, with the test voltage limited to the rating of the insulation. The reading is compared with the manufacturer's data for the insulation system and with earlier results on the same machine, where a decline, even if it remains above a published minimum, suggests contamination or degradation. A low reading is not immediately a failed insulation. The first step is to look for a bridge by checking the connections that were opened, inspecting oil pipes, seals, sensor leads and bolts, and cleaning and retesting. Only if the low reading persists is the insulation suspected. ANSI/NETA ATS-2025 covers acceptance testing of rotating machines and ANSI/NETA MTS-2023 covers maintenance testing; refer to your own licensed copies for the criteria and to the machine manufacturer for bearing-specific data.

Variations

At acceptance the test confirms that the insulation as installed is effective and creates a baseline for later comparison, and it is performed before the machine is coupled and run. In maintenance it is performed after bearing replacement, after reassembly of an insulated housing, and on machines that have shown signs of shaft current damage such as fluting or bearing noise. The machine type changes the details. Large induction motors and generators usually insulate the non-drive end to leave the shaft grounded at the drive end. Machines on variable-frequency drives may have insulation at one or both ends, or special insulated or ceramic bearings, together with a shaft-grounding device that must itself be considered when planning the test. Large synchronous machines may have an insulated bearing pedestal, insulated oil pipes and insulated seals at the same end. In each case the governing standard and the manufacturer's instructions define which parts to test.

Where this test is called for

The equipment classes and standard sections that call for this test, and the UltraDb forms that carry it.

Rotating Machinery and Motor Control

AC Induction Motor and Generator Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.15.1.B.8; ATS-2025 7.15.1.D.8
Synchronous Motor and Generator Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.15.2.B.8; ATS-2025 7.15.2.D.8; MTS-2023 7.15.2.B

Governing standards

Maintenance Testing Specifications for Electrical Power Equipment and Systems

Purchase this standard ↗

Questions

What damage do shaft currents cause in motor bearings?

The current arcs through the thin oil film and erodes small pits in the bearing races and balls or in the journal. Over time the pits form a washboard pattern called fluting, which causes noise, vibration and overheating, and the arcing also breaks down the lubricant. Bearing failure can follow suddenly.

Why is only one end of the machine insulated?

The circulating shaft current needs a closed loop through both bearings and the frame. Insulating one end opens the loop. Insulating both ends would leave the shaft floating, which can allow a voltage to build up on it, so the other end is normally left grounded.

What should I check if the reading comes out low?

First look for a bridge, not for failed insulation: oil lines touching the frame, grounded sensor leads, shaft-grounding devices, missing insulating sleeves or surface contamination. Clean, fix any bridge and retest. Only a low reading that persists points to a damaged insulating layer.

Where do I find the required insulation value for a bearing?

In the machine manufacturer's data and in the governing standards, such as ANSI/NETA ATS-2025 for acceptance and ANSI/NETA MTS-2023 for maintenance. Use your licensed copy and limit the test voltage to the rating of the bearing insulation.

Record this test in UltraDb.

Start free ->

UltraDb references ASTM, ANSI, IEEE, NETA, NFPA, NEMA, FAA, TIA, and IEC standards descriptively, to identify the published methods its forms are built from. UltraDb and Verlecta are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, NFPA, NEMA, FAA, TIA, IEC, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies. Where a standard is sold through the ANSI webstore, Verlecta may earn a commission on a purchase made through our link, at no extra cost to you. A commission never decides which standards we cite or how a form is built.