UltraDb
Log in Get started
<- Reference

Batteries and DC Systems

Valve-Regulated Lead-Acid (VRLA) Battery Acceptance Test

What it is

A VRLA battery acceptance test is a comprehensive electrical and physical evaluation performed on a new or refurbished valve-regulated lead-acid battery system before it is energized and placed into standby or backup service. The test measures the as-received condition of the battery through a series of checks: visual inspection for physical damage, leakage, or manufacturing defects; measurement of individual cell voltages and battery terminal voltage to confirm correct string assembly and proper charge state; verification that the battery is fully charged per the manufacturer's guidance; assessment of the battery's available capacity through a controlled load test; and confirmation that voltage, current, and temperature readings all fall within acceptance criteria. NETA ATS-2025 7.18.1.3 sets the acceptance-test scope and acceptance limits for VRLA batteries across all nominal voltages and capacity ratings used in backup power and uninterruptible power supply (UPS) applications.

Why it is performed

A VRLA battery that is damaged, miswired, undercharged, or equipped with a failing cell will fail or perform poorly the moment it is called upon to supply backup power. An acceptance test performed before the battery is placed into service catches manufacturing defects, shipping damage, improper installation, or battery strings that are not holding charge, so the battery can be repaired, recharged, or replaced before it is relied upon rather than discovered when a real power outage tests it unexpectedly. Confirming rated capacity through a load test also verifies that all cells are contributing equally and that the battery will deliver the current and duration needed for the application.

When it is performed

Acceptance: run on every new VRLA battery system, or on any refurbished battery that has undergone cell replacement or major service, before the battery is first connected to the charging system and load it will support. The test is typically performed after delivery and installation in the field but before the battery is placed into its protective housing or cabinet and integrated into the larger backup-power architecture. If the test reveals a failure, the battery can be repaired or exchanged before the system cutover date.

How it is typically performed

With the battery isolated from all loads, charging systems, and external circuits so it stands as a standalone unit, a technician begins with a visual and physical inspection - checking for cracks, leakage, corrosion, or loose terminals. The battery is then measured at rest to confirm it is fully charged and all cells are present and within an acceptable voltage band of one another; any undercell is noted and the battery is recharged if needed before proceeding. Once the battery is confirmed fully charged, a controlled load (either a calibrated electronic load or a resistive load bank) is connected to the battery terminals, and current is drawn at a rate and for a duration specified by either the manufacturer's published data or, if manufacturer data is not available, by IEEE 1188 standard load-test methodology. Throughout the load test, voltage is monitored continuously and current is recorded; the test continues until either the specified time expires or the battery voltage drops to the minimum end voltage specified by the manufacturer's published data or IEEE 1188, at which point the load is removed and the battery is allowed to recover. Post-test measurements of voltage and cell balance are taken to confirm the battery has not been permanently damaged by the load.

What gets recorded

Equipment identification: manufacturer, model number, battery type, rated capacity (in ampere-hours), nominal system voltage (in VDC), and the equipment designation or location in the facility. As-received condition: visual inspection findings, individual cell voltages, terminal voltage, and ambient temperature at the time of test. Load test data: the load test basis used (manufacturer published data or IEEE 1188), the load current applied (in amps), the load duration (in minutes or hours), the start voltage before load, the minimum voltage reached during load, the end-of-test voltage, and the time at which minimum voltage was reached. Post-test recovery voltage after a specified rest period. Any deficiencies, corrective actions taken (recharged, cells equalized, terminals cleaned), and ambient and test-instrument information needed to audit the result later.

How results are evaluated

NETA ATS-2025 Section 7.18.1.3 establishes acceptance criteria across several dimensions, all of them referenced to the manufacturer's published data or, where manufacturer data is unavailable, to IEEE 1188, rather than to a fixed numeric threshold set by the standard itself. First, the as-received terminal voltage must fall within a manufacturer-specified band that accounts for the number of cells and their nominal individual cell voltage; any cell reading significantly outside the band of its neighbors is flagged for investigation before the load test proceeds. Second, the load-test capacity result - the total ampere-hours or watts delivered before voltage falls to the minimum - is compared against the acceptance basis the manufacturer publishes for that battery, or against IEEE 1188 if no manufacturer data exists; a result that does not meet that basis means the battery has not yet reached its expected performance and may need charging, equalization, or replacement. Third, all post-test recovery voltages must return to within the acceptable band, confirming the battery has not suffered permanent damage. See the purchased standard for the complete acceptance criteria, voltage-band tolerances, and capacity thresholds applicable to the specific battery rating and nominal system voltage under test.

Governing standards

ANSI/NETA ATS-2025

ANSI/NETA ATS-2025

Purchase this standard ↗

Run this test in UltraDb.

Start free ->

UltraDb references ASTM, ANSI, IEEE, and NETA standards descriptively, to identify the published methods its forms are built from. UltraDb and Verlecta are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies.