Transformer, Liquid-Filled

Insulating-Oil Quality Screen (ASTM D117)

Readings at several test points, all inside the allowed error band.

What it is

The Insulating Oil Quality Screen records the ANSI/NETA insulating-liquid battery for one sample on one report, using the ASTM D117 guide as the map of methods: dielectric breakdown by ASTM D1816 (five breakdowns at a 1 mm or 2 mm electrode gap, or a laboratory's reported mean), acid number (ASTM D974 color indicator or ASTM D664 potentiometric), water by coulometric Karl Fischer titration (ASTM D1533) with its reagent, interfacial tension by the ring method (ASTM D971), color on the ASTM D1500 disk scale with its report form, dissipation or power factor at 25 C and 100 C (ASTM D924) and the visual condition in the ASTM D1524 terms. Dissolved gas analysis is not part of the screen; it has its own ASTM D3612 form. The screen is where one of three sampling contexts is selected: new fluid as received (the ASTM type specification), oil received in new equipment (ANSI/NETA ATS 7.2.2, ATS-2025 Table 100.4.1) or in service (ANSI/NETA MTS 7.2.2, MTS-2023 Tables 100.4.1, 100.4.3 and 100.4.5). That selection, with the fluid type and the voltage class, chooses the limit table every property is graded against.

Why it is performed

The liquid inside a transformer or oil-filled switching device insulates the internal parts and carries heat away from the windings or contacts. Moisture, oxidation products, particulates, and dissolved or entrained gases all degrade the liquid's insulating strength and heat-transfer ability, and can originate from a breathing conservator, failed seals, internal arcing that has already begun, or slow oxidative aging during years of service. A quality screen performed in the field captures the liquid's current condition before any of those contaminants progress to an internal breakdown or hotspot. Results that fall outside acceptable bands trigger further investigation, reconditioning, or replacement of the liquid before the equipment is returned to service or left in an unsafe operating state.

When it is performed

Acceptance: new or reconditioned liquid-filled equipment is screened before first energization or after major maintenance such as rewinding, core repair, or tank seal work, as part of the electrical acceptance-test sequence. Maintenance: periodic field screening is performed on in-service equipment - either on a fixed interval (annually, every three years, depending on the equipment's age and duty cycle) or when triggered by an event such as a through-fault, sustained high load, rising dissolved-gas alarms, or visible signs of moisture or contamination. A field screen is also often run ahead of a full laboratory insulating-liquid analysis to decide whether a sample is worth sending to the lab or whether the equipment needs immediate intervention.

How it is typically performed

A representative sample is drawn per ASTM D923: flush the drain valve and extension first, never sample apparatus that has only a drain plug, avoid sampling exposed to the atmosphere in rain or above 50 percent relative humidity, and take water and gas samples in a syringe or a stainless steel cylinder. The laboratory results are entered as the methods report them. The electrode gap is selected first, then the five ASTM D1816 breakdowns; the form computes their mean and the range as a percent of the mean and applies the method's section 9.5 validity check, under which the range must stay below 92 percent of the mean at the 2 mm gap or below 120 percent at the 1 mm gap. A series outside that allowance is not a failed sample but an invalid one: the result stays indeterminate until the series is repeated on a fresh cup filling, or, when no specimen remains, until the reviewing engineer dispositions the report by hand with the mean, the range percent and the reason in the comment. A laboratory report that gives only the average goes in the legacy reported-mean field, which is graded only when no breakdowns are recorded. Water carries the reagent or solvent system, which natural ester and silicone samples require; color carries the disk, the D1500 report form (exact match, L lighter than the disk, L0.5 or D8) and the diluted flag; acid number carries the method used; power factor is entered at both temperatures; the visual condition is entered in the D1524 terms.

What gets recorded

The sampling context, the fluid type and the voltage class (all three required), the electrode gap, the five ASTM D1816 breakdowns with the computed mean, range percent and range excess, the specimen-exhausted flag and the range comment, the legacy reported mean, the acid number and its method, the water content as a whole number in mg/kg with its reagent, the interfacial tension in mN/m, the color disk with its report form and diluted flag, the power factor at 25 C and at 100 C, and the visual appearance, with the site, nameplate, comments and equipment status that every fluid form carries.

How results are evaluated

Every property is graded independently against the table the sampling context selects, and the overall result is the worst property: ASTM D3487-25 Table 1 for new mineral oil as received (ASTM D6871-26 Table 1 and ASTM D4652-20 Table 1 for natural ester and silicone), ANSI/NETA ATS-2025 Table 100.4.1 for mineral oil received in new equipment, by voltage class, and the ANSI/NETA MTS-2023 tables in service (100.4.1 mineral, 100.4.3 silicone, 100.4.5 natural ester). The visual condition is graded on the ASTM D1524 terms: clear and bright passes, every other appearance fails. A result within 10 percent of its limit is reported passed with comments; that marginal band is UltraDb's own convention, not a value from any table, and a value exactly at a printed limit conforms. The D1816 section 9.5 gate decides alone: an invalid or incomplete series makes the whole screen indeterminate whatever the other properties grade to. What the tables do not cover stays visible as ungraded rather than borrowed from another column: natural ester has no interfacial-tension requirement, silicone color is specified on the platinum-cobalt scale rather than the D1500 scale recorded here, neither ester nor silicone has an owned limit for oil received in new equipment, a diluted color reading is reported but not graded, and a non-mineral water result without its reagent is withheld. A blank voltage class is reported indeterminate in the new-equipment and in-service contexts rather than graded against the loosest column, and a fluid type of Other is never graded against the mineral table. The three sampling contexts, the 9.5 gate, the legacy mean and the marginal band are all stated on the form itself.

Where this test is called for

The equipment classes and standard sections that call for this test, and the UltraDb forms that carry it.

Circuit Breakers and Switchers

Automatic Circuit Recloser (Oil/Vacuum) - Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.24.1.B.5; ATS-2025 7.24.1.D.5; MTS-2023 7.24.1.B.5; Table 100.4.1
Medium- and High-Voltage Oil Circuit Breaker Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.6.2.B.6; ATS-2025 7.6.2.D.6; MTS-2023 7.6.2.B; Table 100.4

Reactors

Liquid-Filled Reactor Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.20.3.2.B.7; ATS-2025 7.20.3.2.D.7, Tables 100.4, 100.4.1, 100.4.2, 100.4.3; MTS-2023 7.20.3.2.B

Regulating Apparatus

Step Voltage Regulator Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.12.1.1.B.14; ATS-2025 7.12.1.1.B.14.7; ATS-2025 7.12.1.1.B.15; ATS-2025 7.12.1.1.D.14; ATS-2025 7.12.1.1.D.15; MTS-2023 7.12.1.1.B.12; MTS-2023 7.12.1.1.B.13; Table 100.4
Induction Regulator Voltage-Regulation Field Test Acceptance / Maintenance
Cited in: MTS-2023 7.12.1.2.B.8; MTS-2023 7.12.1.2.D.8; Table 100.4
Load Tap-Changer Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.12.3.B.8; ATS-2025 7.12.3.D.8 / Table 100.4; MTS-2023 7.12.3.B.8

Reclosers and Sectionalizers

Automatic Line Sectionalizers, Oil - Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.24.2.B.4; ATS-2025 7.24.2.D.4 / Table 100.4; MTS-2023 7.24.2.B.4

Switches

Medium-Voltage Oil Switch Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.5.2.B.6; ATS-2025 7.5.2.D.6; MTS-2023 7.5.2.B; Table 100.4.1; Table 100.4.3
Vacuum Switch Medium-Voltage Acceptance Test Acceptance / Maintenance
Cited in: ATS-2025 7.5.3.B.6; ATS-2025 7.5.3.D.6; Table 100.4

Transformer, Liquid-Filled

Liquid-Filled Transformer Acceptance Test Acceptance / Maintenance
Cited in: ASTM D1816-12(2019) 9.4, 9.5, 10; ASTM D1816-12(2019) 9.5; ASTM D3487-25 Table 1 footnote E; ATS-2025 7.2.2.B.14; ATS-2025 7.2.2.D.14; ATS-2025 Table 100.4.1; ATS-2025 Tables 100.4.1, 100.4.2, 100.4.3; ATS-2025 Tables 100.4.1, 100.4.3; MTS-2023 7.2.2.B.14; Table 100.4

Governing standards

ASTM D117

Standard Guide for Sampling, Test Methods, and Specifications for Electrical Insulating Liquids

Purchase this standard ↗

ANSI/NETA ATS 7.2.2

ANSI/NETA ATS 7.2.2

Purchase this standard ↗

ANSI/NETA MTS 7.2.2

ANSI/NETA MTS 7.2.2

Purchase this standard ↗

Run this test in UltraDb.

Start free ->

UltraDb references ASTM, ANSI, IEEE, NETA, NFPA, NEMA, FAA, TIA, and IEC standards descriptively, to identify the published methods its forms are built from. UltraDb and Verlecta are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, NFPA, NEMA, FAA, TIA, IEC, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies. Where a standard is sold through the ANSI webstore, Verlecta may earn a commission on a purchase made through our link, at no extra cost to you. A commission never decides which standards we cite or how a form is built.