The ground detector relay, device 64, senses a ground fault on an ungrounded, high-resistance grounded or direct-current system, where the first ground does not cause a heavy fault current. Testing simulates the ground signal, finds pickup and times the alarm or trip.
Device 64 is the ground detector relay, applied where a ground fault does not announce itself with a large current. That includes ungrounded and high-resistance grounded alternating-current systems, generator and motor stator windings on grounding resistors, and ungrounded direct-current control and battery systems. The relay senses the ground in a different way depending on the application: as residual or neutral displacement voltage across a broken-delta winding or a neutral resistor, as a small neutral current, or as an imbalance of the potential of the direct-current bus to ground measured through a resistor bridge. In many installations it only raises an alarm, because the first ground is not an emergency, and in others it trips. The test confirms that the relay detects a simulated ground at the intended level, acts after the intended delay and reaches the alarm or trip circuit.
On an ungrounded or high-resistance grounded system, a single ground leaves the supply almost undisturbed, which is why it is tolerated. The danger is that it hides: a second ground on another phase or on the opposite pole turns it into a phase-to-phase fault or a short on the control supply, with heavy current, equipment damage and a loss of control power at the worst moment. A ground on a battery system can also falsely operate trip coils or hold devices in. The ground detector gives maintenance staff a chance to find and clear the first ground before the second one arrives. A relay that has gone deaf, a wrongly connected sensing winding or a dead indicator removes that warning without any sign, so periodic testing is the only assurance.
The relay watches the voltage between the system and ground, or the current in the grounding path. In a healthy ungrounded alternating-current system, the three phase voltages are balanced with respect to ground and the residual voltage is close to zero. A ground on one phase shifts the neutral and the residual quantity rises, so a voltage-sensing element connected across a broken-delta secondary operates. In a high-resistance grounded system, the ground current through the neutral resistor develops a voltage that the relay measures. In a direct-current system, two resistors form a bridge from the positive and negative buses to ground, and a ground on either pole unbalances the bridge, which the detector reads. In machine protection, a filtering element rejects the normal third-harmonic voltage so that only a true ground fault operates the relay.
The relay is isolated from the voltage transformer secondaries or the neutral resistor circuit so the test cannot back-feed a live system, and the trip or alarm outputs are blocked or the links opened so that the test does not disturb live equipment. For an alternating-current relay, a relay test set applies a controlled residual voltage, or a neutral voltage of suitable phase and frequency, to the sensing input in the connection the relay expects, raising it gradually to find the pickup and lowering it to find the reset. The delay is measured by applying a step and timing the output. Where harmonic filtering is part of the function, the injected signal is chosen at the right frequency to show that the element responds to the fundamental and not to the filtered component. For a direct-current detector, a ground is simulated by connecting a high-value resistor from one pole to ground in a controlled way, or the instrument's own test function is used, and the indicator and alarm are observed. The sensing connections, the alarm and the trip circuit are proven, the links are restored and the settings are left as found.
The record states the relay type and application, the sensing input used, the pickup and reset readings found and the delay measured. It notes how the ground was simulated, the response of the alarm, indicator and trip outputs, the instrument and its calibration status, the links blocked and restored, and the as-found and as-left settings together with any repair or correction.
The pickup is compared with the setting from the system study, allowing the tolerance published for the relay, and the delay is judged against the set value. The response should be consistent on every sensing input or every pole, since a detector that sees a ground on one side and not the other is miscalibrated or wired wrongly. Results are compared with earlier tests on the same relay to detect drift, and the output is checked for the alarm or trip action the design calls for. ANSI/NETA ATS-2025 and ANSI/NETA MTS-2023 cover the ground detector relay among the protective relay tests. For the tolerances and values, refer to your own licensed copy of those standards and to the relay instruction book.
The equipment classes and standard sections that call for this test, and the UltraDb forms that carry it.
On an ungrounded or high-resistance grounded system, one ground carries little current and does not disturb the supply, so service can continue while it is located. The alarm gives staff a chance to find it before a second ground creates a real fault.
The test set simulates the sensing signal at the relay input, such as a residual voltage, with the relay isolated from the system. On a direct-current detector, a controlled resistor or the built-in test function represents the ground.
It is a set of voltage transformer secondaries connected in a delta with one corner left open. The open corner shows almost no voltage when the system is balanced and shows a residual voltage when a ground appears, which is what the relay measures.
Generators produce a small third-harmonic voltage in normal operation that can look like a ground. Detectors that filter or measure it separately avoid false operation and can also help cover the winding near the neutral.
UltraDb references ASTM, ANSI, IEEE, NETA, NFPA, NEMA, FAA, TIA, and IEC standards descriptively, to identify the published methods its forms are built from. UltraDb and Verlecta are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, NFPA, NEMA, FAA, TIA, IEC, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies. Where a standard is sold through the ANSI webstore, Verlecta may earn a commission on a purchase made through our link, at no extra cost to you. A commission never decides which standards we cite or how a form is built.